GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay

GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay
GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay
GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay
GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay
GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay
GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay
GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay
GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay

GE FANUC 369-HI-R-M-0-0-0-E Multilin Motor Management Relay

This 369-HI-R-M-0-0-0-E Motor Management Relay was manufactured by GE FANUC, In Stock, 100% Guaranteed Brand New and Authentic. Link to More Information

 
Manufacturer:
GE FANUC
Part Number:
369-HI-R-M-0-0-0-E
Country of Origin:
USA
Condition:
New With Original Package
Shipping Port:
ShangHai, Xiamen
Warranty:
12 Months
 

Overview

The 369 Motor Management Relay is an advanced digital relay designed to protect and monitor three-phase motors and their related mechanical systems. One of its standout features is the ability to "learn" specific motor parameters and adapt to individual applications. By analyzing values like motor inrush current, cooling rates, and acceleration time, the 369 Relay enhances its protective functions, offering tailored and efficient motor protection.

Specifications

CONTROL POWER
  • LO Range:
    • DC: 20 to 60 V DC
    • AC: 20 to 48 V AC at 50/60 Hz
  • HI Range:
    • DC: 50 to 300 V DC
    • AC: 60 to 265 V AC at 50/60 Hz
  • Power:
    • Nominal: 20 VA
    • Maximum: 65 VA
  • Holdup:
    • Non-failsafe trip: 200 ms
    • Failsafe trip: 100 ms
FUSE
  • Type: T 3.15 A H 250 V (5 × 20 mm)
  • Specifications: Timelag high breaking capacity
PHASE CURRENT INPUTS (CT)
  • CT Input (Rated): 1 A and 5 A secondary
  • CT Primary: 1 to 5000 A
  • Range:
    • For 50/60 Hz nominal frequency: 0.05 to 20 × CT primary amps
    • For variable frequency: 0.1 to 20 × CT primary amps
  • Full Scale: 20 × CT primary amps or 65535 A maximum
  • Frequency: 20 to 100 Hz
  • Conversion: True RMS, 1.04 ms/sample
  • Accuracy:
    • At ≤ 2 × CT:
      • ±0.5% of 2 × CT for 50/60 Hz nominal frequency
      • ±1.0% of 2 × CT for variable frequency (for sinusoidal waveforms)
    • At > 2 × CT:
      • ±1.0% of 20 × CT for 50/60 Hz nominal frequency
      • ±3.0% of 12 × CT or less for variable frequency (for sinusoidal waveforms)
DIGITAL / SWITCH INPUTS
  • Inputs: 6 optically isolated
  • Input Type: Dry Contact (< 800 Ω)
  • Function: Programmable
GROUND CURRENT INPUT (GF CT)
  • CT Input (Rated): 1 A/5 A secondary and 50:0.025
  • CT Primary: 1 to 5000 A (1 A/5 A)
  • Range:
    • 0.1 to 1.0 × CT primary (1 A/5 A)
    • 0.05 to 25.0 A (50:0.025)
  • Full Scale:
    • 1.0 × CT primary (1 A/5 A)
    • 25 A (50:0.025)
  • Frequency: 20 to 100 Hz
  • Conversion: True RMS 1.04 ms/sample
  • Accuracy at 50/60 Hz:
    • For 1 A/5 A: ±1.0% of full scale (1 A/5 A)
    • For 50:0.025: ±0.07 A at <1 A, ±0.20 A at <25 A
  • Accuracy at Variable Frequency:
    • For 1 A Tap:
      • ±1.5% for 40 to 100 Hz
      • ±2.5% for 20 to 39 Hz
    • For 5 A Tap:
      • ±2% for 40 to 100 Hz
      • ±3% for 20 to 39 Hz
    • For 50:0.025:
      • ±0.2 A at <1 A
      • ±0.6 A at <25 A
PHASE/LINE VOLTAGE INPUT (VT) (OPTION M)
  • VT Ratio: 1.00 to 240.00:1 in steps of 0.01
  • VT Secondary: 240 V AC (full scale)
  • Range: 0.05 to 1.00 × full scale
  • Frequency: 20 to 100 Hz
  • Conversion: True RMS 1.04 ms/sample
  • Accuracy:
    • ±2.5% of full scale for ≤ 200 V at 20 to 39 Hz
    • ±1% of full scale for 12 to 240 V at > 40 Hz
  • Burden: >200 kΩ
  • Max. Continuous: 280 V AC
BSD INPUTS (OPTION B)
  • Frequency: 1 to 120 Hz
  • Dynamic BSD Range: 20 mV to 480 V RMS
  • Accuracy: ±0.02 Hz
  • Burden: >200 kΩ
RTD INPUTS (OPTION R)
  • Wire Type: 3 wire
  • Sensor Type: 100 Ω platinum (DIN 43760), 100 Ω nickel, 120 Ω nickel, 10 Ω copper
  • RTD Sensing Current: 3 mA
  • Range: –40 to 200°C or –40 to 392°F
  • Accuracy: ±2°C or ±4°F
  • Lead Resistance: 25 Ω max. per lead for Pt and Ni type; 3 Ω max. per lead for Cu type
  • Isolation: 36 Vpk
AMBIENT TEMPERATURE
  • Operating Range: –40°C to +60°C
  • Storage Range: –40°C to +80°C
  • T-Code Rating: T4A (for MOD 502 only)
    • Note: For 369 units with the Profibus, Modbus/TCP, or DeviceNet option:
      • Operating Range: +5°C to +60°C
      • Storage Range: +5°C to +80°C
HUMIDITY
  • Specification: Up to 95% non-condensing
DUST/MOISTURE
  • Protection: IP50
Schnelle Angebote Erhalten Sie Preis & Verfügbarkeit SCHNELL von unserem engagierten Kundenserviceteam.
Lieferung Schnellversand, Fracht- und internationaler Versand verfügbar.
Bedingung 100% Neu mit Originalverpackung
Zahlung Wir akzeptieren American Express, Discover, MasterCard, PayPal und Visa. Unsere Seite ist durch RapidSSL gesichert.
Versandhafen Shanghai, Xiamen
Garantie 12 Monate
Q: Sind unsere Preise wettbewerbsfähig?
A: Ja, wir arbeiten mit über 50 Ländern weltweit zusammen. Als führender Lieferant in China bieten wir basierend auf den Markttrends erhebliche Rabatte an.
Q: Wie lange ist die Garantiezeit?
A: Alle unsere neuen und originalen Produkte haben eine standardmäßige einjährige Garantie.
Q: Welche Zahlungsmethoden akzeptieren wir?
A: Wir verlangen 100 % T/T (Telegraphische Überweisung) vor dem Versand. Bei Artikeln mit längerer Lieferzeit ist eine Anzahlung von 30 % im Voraus erforderlich, der Rest von 70 % ist vor dem Versand fällig. Wenn Sie einen Vertreter in China haben, können Sie die RMB-Überweisung über ihn arrangieren.
Q: Welche Versandmethoden verwenden wir?
A: Wir verwenden hauptsächlich FedEx, DHL, UPS und BRE für den Versand. Wenn Sie ein Konto bei einem dieser Anbieter haben, können Sie den Versand direkt abwickeln. Wir bieten auch kostenlosen Versand an in China ansässige Spediteure.
Q: Wie lange ist unsere Lieferzeit?
A: Die Lieferung erfolgt in der Regel 1-3 Tage nach Erhalt der Anzahlung. Bei Artikeln mit längerer Lieferzeit erfolgt der Versand gemäß dem angegebenen Zeitplan.
Q: Wie verpacken wir die Waren?
A: Wir sorgen für sichere Verpackung mit mehreren Schutzschichten. Die Produkte werden zuerst in ihre Originalverpackungen gelegt und mit Etiketten versiegelt. Anschließend wird eine Schicht Luftpolsterfolie zum Schutz vor Stößen während des Transports hinzugefügt. Schließlich werden die Artikel sicher in robusten Kartons verpackt.
Q: Wie können Kunden uns kontaktieren und ein Angebot anfordern?
A: Sie können uns per E-Mail, WhatsApp, WeChat, Skype oder Ihrer bevorzugten Kommunikationsplattform erreichen. Kontaktieren Sie uns mit Ihren Anforderungen, und wir erstellen Ihnen ein schnelles, maßgeschneidertes Angebot.
 

Kürzlich angesehen

Express Shipping icon
Expressversand
Schnelle Lieferung für Ihre dringenden Anforderungen.
Large stock icon
Umfangreiches Inventar
Großer Lagerbestand für sofortigen Versand.
Quality Assurance Icon
Qualitätssicherung
Authentische, hochwertige PLC- und DCS-Komponenten.
Global Service icon
Globaler Service
Unterstützung von Kunden weltweit mit zuverlässigem Service.