{"product_id":"abb-ai820-3bse008544r1-s800-io-bipolar-analog-input-module","title":"ABB AI820 3BSE008544R1 S800 IO Bipolar Analog Input Module","description":"\u003ch2\u003eABB AI820 S800 I\/O Differential Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for differential analog signal acquisition in ABB System 800xA and S800 I\/O systems, the \u003cstrong\u003eABB AI820\u003c\/strong\u003e (\u003cstrong\u003eAI820\u003c\/strong\u003e Analog Input Module, Article Number \u003cstrong\u003e3BSE008544R1\u003c\/strong\u003e) provides direct physical\/electrical execution across four bipolar current or voltage channels. The unit converts +\/-20 mA or +\/-10 V field inputs into 12-bit digital values, distributing external 24 VDC transmitter power through extended Module Termination Units (MTUs) to direct 2-wire field instruments. Onboard current-sensing circuits feature 5 W rated 250 Ohm resistors to protect single channels against accidental 30 VDC overvoltage faults.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eAI820\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eArticle Number\u003c\/td\u003e\n\u003ctd\u003e3BSE008544R1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eSwitzerland\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.2 kg (0.44 lbs)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e45 mm x 119 mm x 102 mm (1.77 in x 4.68 in x 4.01 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to +55 deg C (+32 deg F to +131 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e+5 V ModuleBus: Max 100 mA; +24 V external supply: Max 260 mA (Typ. 1.7 W to 6 W)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e4 differential bipolar channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Ranges\u003c\/td\u003e\n\u003ctd\u003e-20 mA to +20 mA, 0-20 mA, 4-20 mA, -10 V to +10 V, 0-10 V, 2-10 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Resistance\u003c\/td\u003e\n\u003ctd\u003e250 Ohm (current mode), 200 kOhm (voltage mode)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA\/D Resolution\u003c\/td\u003e\n\u003ctd\u003e12-bit including sign\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConversion Time\u003c\/td\u003e\n\u003ctd\u003eLess than or equal to 1.5 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Isolation\u003c\/td\u003e\n\u003ctd\u003eGroupwise isolated from ground (Rated Insulation Voltage = 50 V)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Normal Mode Voltage\u003c\/td\u003e\n\u003ctd\u003e30 VDC continuous protection per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEnclosure Rating\u003c\/td\u003e\n\u003ctd\u003eIP20 (IEC 60529)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHazardous Location Class\u003c\/td\u003e\n\u003ctd\u003eATEX Zone 2, cULus Class 1 Div 2 \/ Zone 2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eDeterministic ModuleBus Execution and Input Overvoltage Protection\u003c\/h3\u003e\n\u003cp\u003eThe AI820 transmits acquired process image data over the backplane using deterministic backplane bus communication velocity, achieving complete input loop conversion cycles within 1.5 ms. Firmware flash compatibility ensures seamless communication synchronization with cluster controllers across the S800 backplane. Built-in thermal dissipation limits on the 250 Ohm current sense resistors withstand temporary 24 VDC cross-connection events, while groupwise galvanic isolation isolates field signal ground loops from sensitive ModuleBus digital components.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How does the AI820 protect its input circuitry if 24 VDC loop power is accidentally miswired to a current input?\u003c\/p\u003e\n\u003cp\u003eA: Each current input relies on robust 5 W rated 250 Ohm sense resistors designed to absorb temporary 30 VDC normal mode overvoltage conditions on a single channel without destroying the input stage.\u003c\/p\u003e\n\u003cp\u003eQ: Are transmitter power supply terminals on the AI820 module current-limited?\u003c\/p\u003e\n\u003cp\u003eA: No. When distributing process power to 2-wire transmitters via extended MTU baseplates, the transmitter power terminals carry no internal current limiting and must rely on external power supply protection.\u003c\/p\u003e\n\u003cp\u003eQ: Can channels on the AI820 be configured independently for current or voltage measurement?\u003c\/p\u003e\n\u003cp\u003eA: Yes. Each of the four differential channels can be individually selected for current (-20 mA to +20 mA) or voltage (-10 V to +10 V) operation in software.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eMount the S800 terminal unit onto a standard 35 mm DIN rail, verifying that the integrated grounding clip maintains low-impedance contact with an unpainted metal section of the rail. Insert the AI820 module straight into the MTU guide slots, pressing firmly until the locking latches secure the module in place.\u003c\/p\u003e\n\u003cp\u003eWire signal leads to the correct differential input terminals, paying strict attention to polarity for bipolar voltage and current loops. Connect shielded cables to the main ground bar via low-impedance grounding clamps. When powering 2-wire field transmitters directly from the module termination unit, ensure the external 24 VDC process power supply incorporates dedicated branch fusing. Keep at least 50 mm of vertical ventilation space above and below the module enclosure for natural thermal dissipation up to +55 deg C ambient operating limits.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":53005110411576,"sku":"AI809","price":188.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0893\/1616\/3896\/files\/647.jpg?v=1790042320","url":"https:\/\/www.automodulexpert.com\/products\/abb-ai820-3bse008544r1-s800-io-bipolar-analog-input-module","provider":"AutoModuleXpert Ltd.","version":"1.0","type":"link"}