{"product_id":"abb-imcpm03-bailey-infi-90-communication-port-module","title":"ABB IMCPM03 Bailey INFI 90 Communication Port Module","description":"\u003ch2\u003eABB IMCPM03 Bailey INFI 90 Communication Port Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eABB IMCPM03\u003c\/strong\u003e is a communication port module designed for ABB Bailey INFI 90 and Symphony DCS platforms, including the INFI 90 OPEN system. It serves as an isolated configuration and diagnostic interface, establishing serial communication links between engineering workstations, configuration terminals, operator consoles, and system control buses.\u003c\/p\u003e\n\u003ch3\u003eHardware Architecture and Processing\u003c\/h3\u003e\n\u003cp\u003eBuilt on a 32-bit microprocessor operating at 16 MHz with a 16-bit external bus, the module integrates 256 KB of ROM and 512 KB of RAM. It features direct memory access (DMA) circuitry to efficiently process cyclic and acyclic data exchange without overloading the main processor. The internal memory supports a database capacity of up to 3,000 point definitions.\u003c\/p\u003e\n\u003ch3\u003eInterfaces and Bus Communication\u003c\/h3\u003e\n\u003cp\u003eThe module provides two isolated RS-232-C serial communication channels supporting data transfer rates up to 19.2 kbaud. Physical serial connections include a DB-25 computer interface connector, a DB-9 engineering workstation connector, and a 5-pin round configuration terminal interface (CTT). System-side backplane communication operates over the Controlway bus at 1 Mbps or the Module Bus at 83.33 kbps.\u003c\/p\u003e\n\u003ch3\u003eOperating Power and Diagnostics\u003c\/h3\u003e\n\u003cp\u003ePowered by a +5 VDC supply, the unit draws 750 mA typical (810 mA maximum) with a typical power dissipation of 3.8 W. On-board diagnostics run continuous hardware tests, reporting status through one dual-color LED and eight red diagnostic LEDs on the front panel.\u003c\/p\u003e\n\u003ch3\u003ePhysical and Environmental Requirements\u003c\/h3\u003e\n\u003cp\u003eDesigned for single-slot installation within an INFI 90 OPEN Module Mounting Unit (MMU), the module measures 279.4 × 76.2 × 355.6 mm and weighs 0.68 kg. It operates in non-hazardous environments from 0 deg C to +70 deg C with non-condensing relative humidity rated from 5 to 90 percent (up to 55 deg C) and 5 to 40 percent (at 70 deg C).\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIMCPM03\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB Bailey\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eCommunication Port Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Series\u003c\/td\u003e\n\u003ctd\u003eBailey INFI 90\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eINFI 90 OPEN DCS, Symphony DCS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProcessor\u003c\/td\u003e\n\u003ctd\u003e32-bit microprocessor (16 MHz, 16-bit external bus)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOn-Board Memory\u003c\/td\u003e\n\u003ctd\u003e256 KB ROM, 512 KB RAM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDatabase Capacity\u003c\/td\u003e\n\u003ctd\u003eUp to 3,000 point definitions\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSerial Channels\u003c\/td\u003e\n\u003ctd\u003e2 isolated RS-232-C channels (also supports RS-485 interface)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBaud Rate\u003c\/td\u003e\n\u003ctd\u003eUp to 19.2 kbaud\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eComputer Interface\u003c\/td\u003e\n\u003ctd\u003eDB-25 connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWorkstation Interface\u003c\/td\u003e\n\u003ctd\u003eDB-9 connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Interface\u003c\/td\u003e\n\u003ctd\u003e5-pin round connector (CTT)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Bus Compatibility\u003c\/td\u003e\n\u003ctd\u003eControlway (1 Mbps) \/ Module Bus (83.33 kbps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply\u003c\/td\u003e\n\u003ctd\u003e+5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e750 mA typical, 810 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e3.8 W typical, 4.1 W maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiagnostic Display\u003c\/td\u003e\n\u003ctd\u003e1 dual-color LED, 8 red LEDs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInstallation Slot\u003c\/td\u003e\n\u003ctd\u003eSingle slot, INFI 90 OPEN Module Mounting Unit (MMU)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5-90 % up to 55 deg C; 5-40 % at 70 deg C (non-condensing)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAltitude Limit\u003c\/td\u003e\n\u003ctd\u003eSea level to 3,000 m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.68 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (H × W × D)\u003c\/td\u003e\n\u003ctd\u003e279.4 × 76.2 × 355.6 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCertifications\u003c\/td\u003e\n\u003ctd\u003eCSA certified (ordinary, non-hazardous locations)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What physical connectors are available on the IMCPM03 front panel for serial links? A: The board provides a DB-25 connector for computer interfacing, a DB-9 connector for an engineering workstation, and a 5-pin round connector for a configuration terminal (CTT).\u003c\/p\u003e\n\u003cp\u003eQ: What system buses does the IMCPM03 module use to communicate with the DCS backplane? A: It connects to the system backplane via either the Controlway bus operating at 1 Mbps or the Module Bus operating at 83.33 kbps.\u003c\/p\u003e\n\u003cp\u003eQ: What is the maximum database point capacity supported by the board memory? A: The internal 512 KB RAM and processor architecture support a database capacity of up to 3,000 point definitions.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":51328471335224,"sku":"IMCPM03","price":200.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0893\/1616\/3896\/files\/966.jpg?v=1794275937","url":"https:\/\/www.automodulexpert.com\/products\/abb-imcpm03-bailey-infi-90-communication-port-module","provider":"AutoModuleXpert Ltd.","version":"1.0","type":"link"}