ABB CI810A 3BSE013262R1 AF100 Field Communication Interface Module
The ABB CI810A 3BSE013262R1 serves as the primary CI810A Field Communication Interface Module utilized to execute high-speed AF100 fieldbus traffic management across S800 I/O and Advant/800xA platforms. Equipped with an onboard 16 MHz processor, 0.5 MB FPROM, and 0.5 MB SRAM, the hardware coordinates deterministic data exchange between distributed I/O clusters and host controllers through two integrated AF100 modems with full media cable redundancy.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CI810A |
| Part Number | 3BSE013262R1 |
| Brand | ABB |
| Origin | Switzerland |
| Weight | 0.56 kg |
| Dimensions | 102 mm x 127 mm x 178 mm |
| Operating Temp | -25 deg C to +70 deg C |
| Power Consumption | 3.6 W at 24 VDC |
| System Platform | S800 I/O / Advant OCS / System 800xA |
| Protocol | Advant Fieldbus 100 (AF100) |
| Processor Speed | 16 MHz |
| Memory Capacity | 0.5 MB FPROM / 0.5 MB SRAM |
| Modem Configuration | Dual AF100 Modems |
Backplane Bus Communication Velocity & Media Redundancy
The CI810A interface engine links directly to the S800 I/O module bus structure, driving low-latency data polling across connected I/O stations while maintaining fixed cycle times. Dual onboard AF100 modems drive physical signal transmission over separate coaxial or twisted-pair physical channels. When operating in a cable-redundant configuration, the internal communication logic continuously evaluates signal integrity on both physical lines, instantly transferring active bus traffic to the secondary channel upon detecting physical link degradation or line disconnection without interrupting controller task execution.
Frequently Asked Questions
Q: How does cable redundancy operate across the dual AF100 modems on the CI810A?
A: Both integrated modems receive incoming network frames simultaneously, allowing the hardware to switch active data paths seamlessly at the packet layer if one cable experiences open-circuit or short-circuit failures.
Q: What mounting configurations support the physical housing of the CI810A module?
A: The physical housing installs directly onto standard DIN rails or inside S800 I/O cabinet module termination structures, engaging the backplane bus headers for power and internal signal distribution.
Q: Does the onboard memory require battery backup during system power outages?
A: System firmware and configuration parameters store permanently in the 0.5 MB non-volatile FPROM, while runtime data buffers utilize 0.5 MB SRAM refreshed continuously via the 24 VDC backplane supply.
Field Installation Guidelines
Mount the CI810A module vertically onto the mounting rail assembly inside an IP20 or higher enclosure, ensuring that top and bottom vents retain a minimum 50 mm clearance gap to allow natural air convection across the -25 deg C to +70 deg C operating window. Ground all AF100 network cable shields directly to the cabinet earth grounding bar using low-impedance grounding clamps located near the entry point to mitigate high-frequency electrical noise interference. Verify that both physical AF100 channel connectors seat completely onto the module modems before applying power. Route power wires away from communication lines to prevent electromagnetic coupling into the AF100 signal drivers.
| Quick Quotes | Receive price & availability FAST from our dedicated customer service team. |
|---|---|
| Delivery | Expedited, Freight, And International Shipping Available. |
| Condition | 100% New with Original Package |
| Payment | We accept American Express, Discover, MasterCard, PayPal, and Visa. Our site is secured by RapidSSL. |
| Shipping Port | ShangHai, Xiamen |
| Warranty | 12 Months |
| Q: Is Our Pricing Competitive? |
| A: Yes, we collaborate with over 50 countries worldwide. As a top supplier in China, we offer significant discounts based on market trends. |
| Q: What Is the Warranty Period? |
| A: All our new and original products come with a standard one-year warranty. |
| Q: What Payment Methods Do We Accept? |
| A: We require 100% T/T (Telegraphic Transfer) payment before shipping. For items with a lead time, a 30% deposit is needed upfront, and the remaining 70% is due before shipping. If you have a representative in China, you can arrange an RMB transfer through them. |
| Q: What Shipping Methods Do We Use? |
| A: We primarily use FedEx, DHL, UPS, and BRE for shipping. If you have an account with any of these carriers, you can handle shipping directly. We also offer free shipping to China-based freight forwarders. |
| Q: What Is Our Delivery Time? |
| A: Delivery usually takes 1-3 days after receiving the initial payment. For items with a lead time, shipping will occur according to the specified schedule. |
| Q: How Do We Package the Goods? |
| A: We ensure safe packaging with multiple layers of protection. Products are first placed in their original boxes and sealed with labels. A layer of bubble wrap is then added for collision protection during transit. Finally, the items are packed securely in durable boxes. |
| Q: How Can Customers Contact Us and Request a Quote? |
| A: You can reach out to us via email, WhatsApp, WeChat, Skype, or your preferred communication platform. Contact us with your needs, and we'll provide a prompt, customized quote. |