{"product_id":"general-electric-ur-6tv-temperature-input-module","title":"General Electric UR 6TV Temperature Input Module","description":"\u003cp\u003eThe \u003cstrong\u003eGeneral Electric UR 6TV\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003e6TV\u003c\/strong\u003e Temperature Input Module, operates as a dedicated hardware component for high-precision thermal monitoring within Multilin Universal Relay (UR) platforms. This module provides 8 universal input channels, enabling the acquisition of temperature data from diverse field sensors to support critical thermal protection and equipment monitoring functions in electrical power systems.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eUR 6TV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGeneral Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.38 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e125 mm x 85 mm x 32 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003ePassive signal conditioning\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e8 universal temperature inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Type\u003c\/td\u003e\n\u003ctd\u003eTemperature Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Platform\u003c\/td\u003e\n\u003ctd\u003eMultilin Universal Relay (UR)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBackplane Bus Communication and Signal Isolation\u003c\/h3\u003e\n\u003cp\u003eThe UR 6TV integrates directly with the UR backplane bus, allowing the host relay to process thermal data in real-time alongside other electrical variables. The module features robust galvanic isolation for each input channel, which ensures noise immunity when monitoring sensors located in high-electromagnetic interference environments such as transformer vaults or turbine halls. Firmware flash compatibility is managed via the relay’s system software; engineers must confirm that the current chassis configuration supports the 6TV module to ensure correct data register mapping and alarm setpoint thresholds.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Can the 8 universal channels handle different sensor types simultaneously?\u003c\/p\u003e\n\u003cp\u003eA: Yes. The UR 6TV is designed to support multiple sensor types across its 8 channels, allowing for mixed-signal configurations such as RTDs and thermocouples depending on the specific relay programming.\u003c\/p\u003e\n\u003cp\u003eQ: Is this module capable of hot-swapping while the relay is in operation?\u003c\/p\u003e\n\u003cp\u003eA: No. The UR 6TV is not designed for hot-swapping. The relay must be fully de-energized to prevent electrical damage to the backplane connectors and to ensure that sensor input readings remain stable during the maintenance process.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eEnsure the Multilin UR relay chassis is completely isolated from all power sources before beginning installation.\u003c\/li\u003e\n\u003cli\u003eAlign the UR 6TV module with the designated slot guides in the chassis to prevent pin damage during insertion.\u003c\/li\u003e\n\u003cli\u003eSeat the module firmly into the backplane, ensuring the connector makes full contact before securing the front-panel captive mounting screws.\u003c\/li\u003e\n\u003cli\u003eConnect field sensor wiring to the terminal blocks, ensuring proper shielding is maintained to ground to minimize noise induction.\u003c\/li\u003e\n\u003cli\u003eUse the EnerVista UR software to map the physical channels and define the specific sensor types for each input.\u003c\/li\u003e\n\u003cli\u003eVerify channel status and temperature readings via the relay’s front panel interface to confirm accurate signal conversion before assigning protection thresholds.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"GE FANUC","offers":[{"title":"Default Title","offer_id":52620239929656,"sku":"UR 6TV","price":220.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0893\/1616\/3896\/files\/UR67H_75289d39-301a-42b0-8b0b-a4f1740cb97a.jpg?v=1783497528","url":"https:\/\/www.automodulexpert.com\/products\/general-electric-ur-6tv-temperature-input-module","provider":"AutoModuleXpert Ltd.","version":"1.0","type":"link"}