{"product_id":"honeywell-fs-tsai-1620m-safety-manager-16-channel-module","title":"Honeywell FS-TSAI-1620M Safety Manager 16 Channel Module","description":"\u003ch2\u003eHoneywell FS-TSAI-1620M Safety Manager Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eThe Honeywell \u003cstrong\u003eFS-TSAI-1620M\u003c\/strong\u003e is a 16-channel analog input module engineered for Honeywell Safety Manager systems. It conditions and converts field analog signals for process monitoring in safety-critical and standard industrial control environments. Arranged into two isolated groups of eight channels sharing a common 0 V connection, the module supports both active and passive 0-20 mA and 4-20 mA current transmitters.\u003c\/p\u003e\n\u003ch3\u003eSignal Conditioning and Transmitter Interfaces\u003c\/h3\u003e\n\u003cp\u003eEach input channel incorporates a high-precision 250 ohm resistor (±1%) that provides linear current-to-voltage signal conversion with an overall accuracy of ±0.1% of full scale. Integrated current-limited power distribution allows the module to safely power passive field transmitters. Interfacing with control hardware is accomplished using SICC-0001\/Lx system interconnection cables, while individual shield terminals are provided for each signal line to reduce noise interference.\u003c\/p\u003e\n\u003ch3\u003eElectrical and Mounting Specifications\u003c\/h3\u003e\n\u003cp\u003eThe unit operates from an external 24 V DC power supply, with dedicated screw terminals provided for external power monitoring. Designed for DIN EN rail mounting (TS32 \/ TS35 x 7.5), the compact housing measures 210 x 70 x 60 mm and weighs 0.2 kg. It is rated for extreme operating temperatures ranging from -40 deg C to +85 deg C and complies with Class I, Division 2 standards for hazardous locations.\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFS-TSAI-1620M\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eField Termination Assembly \/ Analog Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e16 channels (2 groups of 8 with common 0 V)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Signal Types\u003c\/td\u003e\n\u003ctd\u003e0 - 20 mA, 4 - 20 mA DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Resistance\u003c\/td\u003e\n\u003ctd\u003e250 ohm (±1%)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConversion Accuracy\u003c\/td\u003e\n\u003ctd\u003e±0.1% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTransmitter Support\u003c\/td\u003e\n\u003ctd\u003eActive and passive types (current-limited distribution)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Interface Cable\u003c\/td\u003e\n\u003ctd\u003eSICC-0001\/Lx system interconnection cable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHazardous Area Rating\u003c\/td\u003e\n\u003ctd\u003eClass I, Division 2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCertifications\u003c\/td\u003e\n\u003ctd\u003eCE, UL, CSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to +85 deg C (-40 to +185 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (L x W x H)\u003c\/td\u003e\n\u003ctd\u003e210 x 70 x 60 mm (8.26 x 2.76 x 2.36 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.2 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCountry of Origin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How are the input channels organized on the FS-TSAI-1620M module?\u003c\/p\u003e\n\u003cp\u003eA: The 16 analog input channels are split into two distinct groups of eight channels, each referencing a common 0 V line.\u003c\/p\u003e\n\u003cp\u003eQ: What input signal ranges and accuracies does the FS-TSAI-1620M support?\u003c\/p\u003e\n\u003cp\u003eA: It accepts standard 0-20 mA and 4-20 mA DC current signals, using a 250 ohm (±1%) internal precision resistor per channel to achieve a conversion accuracy of ±0.1% of full scale.\u003c\/p\u003e\n\u003cp\u003eQ: How is the module connected to the Safety Manager system hardware?\u003c\/p\u003e\n\u003cp\u003eA: The module connects to the system using Honeywell SICC-0001\/Lx system interconnection cables, with individual terminals assigned for signal shielding.\u003c\/p\u003e","brand":"HONEYWELL","offers":[{"title":"Default Title","offer_id":51024075260216,"sku":"FS-TSAI-1620M","price":150.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0893\/1616\/3896\/files\/FS-TSAI-1620M.jpg?v=1755569006","url":"https:\/\/www.automodulexpert.com\/products\/honeywell-fs-tsai-1620m-safety-manager-16-channel-module","provider":"AutoModuleXpert Ltd.","version":"1.0","type":"link"}