{"product_id":"honeywell-mu-tdod52-51304423-200-digital-output-card","title":"Honeywell MU-TDOD52 51304423-200 Digital Output Card","description":"\u003ch2\u003eHoneywell MU-TDOD52 51304423-200 Digital Output Modules\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell MU-TDOD52 51304423-200\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eMU-TDOD52\u003c\/strong\u003e Digital Output Module, operates as a dedicated hardware component for high-density discrete switching within Honeywell Experion PKS and TDC 3000 systems. It drives field devices including solenoids, relays, and actuators across 32 isolated output channels at a nominal operating level of 24 VDC. Integrated optical isolation barriers and surge suppression circuits isolate system control logic from field-side electrical transients and inductive kickback voltages.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eMU-TDOD52\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e51304423-200\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCategory\u003c\/td\u003e\n\u003ctd\u003eDigital Output Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.58 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e255 x 140 x 55 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e3.2 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Density\u003c\/td\u003e\n\u003ctd\u003e32 Isolated Digital Output Channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Type\u003c\/td\u003e\n\u003ctd\u003eOptical Isolation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eExperion PKS \/ TDC 3000\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eDCS Process Control \u0026amp; Digital Output Switching\u003c\/h3\u003e\n\u003cp\u003eThe module provides direct physical drive execution for final control elements using 24 VDC output switching logic. Internal channel-to-channel isolation networks block ground loop propagation between field loads and backplane processing units. Transient surge suppression hardware clamps inductive voltage spikes generated during solenoid or relay coil de-energization. Real-time LED status indicators display channel state and fault conditions, enabling rapid field verification without interrupting control loop processing.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How does the module protect internal DCS logic circuits from inductive load transients?\u003c\/p\u003e\n\u003cp\u003eA: Integrated surge protection diodes and optical isolation barriers suppress high-voltage flyback spikes caused by de-energizing field solenoids or relay coils.\u003c\/p\u003e\n\u003cp\u003eQ: What power source energizes the 24 VDC digital output channels?\u003c\/p\u003e\n\u003cp\u003eA: Field output channels receive power from an external dual-redundant 24 VDC field power supply wired directly to the assembly's power terminal connections.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eIsolate all 24 VDC field power sources before connecting or disconnecting field wiring terminals on the assembly. Strip field conductors to 7 mm and clamp them tightly in screw terminals, verifying that no stray wire strands extend past the terminal housing. Separate field output cabling from sensitive high-level analog wiring and AC power distribution cables by at least 300 mm to suppress crosstalk. Connect cable shield drain wires directly to the main cabinet earth bus bar to ensure effective grounding.\u003c\/p\u003e","brand":"HONEYWELL","offers":[{"title":"Default Title","offer_id":51284212777272,"sku":"MU-TDOD52 51304423-200","price":250.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0893\/1616\/3896\/files\/595_9ba94d21-17ca-45b4-b2c2-a850e43aa54e.jpg?v=1791598878","url":"https:\/\/www.automodulexpert.com\/products\/honeywell-mu-tdod52-51304423-200-digital-output-card","provider":"AutoModuleXpert Ltd.","version":"1.0","type":"link"}