{"product_id":"trusted-tmr-processor-module-ics-triplex-t8110b","title":"Trusted TMR Processor Module | ICS Triplex T8110B","description":"\u003ch2\u003eICS Triplex T8110B Trusted TMR Processor Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eICS Triplex T8110B\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eT8110\u003c\/strong\u003e Trusted TMR Processor, operates as a dedicated hardware component for executing high-integrity safety logic algorithms within Trusted Safety System racks. The unit processes field inputs, manages triple-redundant bus synchronization, and coordinates fault-tolerant output decisions through continuous 2-out-of-3 voting logic.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eT8110B\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eICS Triplex\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e2.81 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e220 mm x 40 mm x 150 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003ePowered via Redundant Backplane Rails\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMemory\u003c\/td\u003e\n\u003ctd\u003e16 MB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eClock Speed\u003c\/td\u003e\n\u003ctd\u003e25 MHz \/ 100 MHz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety Rating\u003c\/td\u003e\n\u003ctd\u003eSIL3 Certified (IEC 61508)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Interfaces\u003c\/td\u003e\n\u003ctd\u003eRS232 Diagnostic Port, Configurable RS422 \/ RS485 Ports\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTime Synchronization\u003c\/td\u003e\n\u003ctd\u003eIRIG-B002 and IRIG-B122 Signals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eTriple Modular Redundancy (TMR) Architecture\u003c\/h3\u003e\n\u003cp\u003eBuilt around a Hardware Implemented Fault Tolerant (HIFT) architecture, the T8110B maintains SIL3 certification compliance across mission-critical execution loops. The processor module incorporates triple modular redundancy (TMR) 2oo3 architecture to evaluate incoming field data, system states, and internal memory routines simultaneously. Complete galvanic isolation separates central processor circuits from external field interfaces and backplane noise. When an internal fault occurs on any single channel, integrated voting circuits isolate the degraded execution path instantly, enforcing fail-safe state execution without interrupting active safety logic operations.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does replacing a faulted T8110B module require reloading application software?\u003c\/p\u003e\n\u003cp\u003eA: No, the module supports full hot replacement. Upon insertion into an active chassis, the standby processor synchronizes application memory and execution state data automatically from the active TMR set without reloading firmware or logic files manually.\u003c\/p\u003e\n\u003cp\u003eQ: What serial time synchronization formats does the T8110B revision support?\u003c\/p\u003e\n\u003cp\u003eA: The T8110B revision includes hardware support for unmodulated IRIG-B002 and modulated IRIG-B122 time synchronization inputs to align system clock timestamps across distributed safety network nodes.\u003c\/p\u003e\n\u003cp\u003eQ: How does the unit indicate hardware fault status locally?\u003c\/p\u003e\n\u003cp\u003eA: The front panel includes dedicated diagnostic status LEDs and active\/standby fault contacts that open or close physically upon detecting module hardware degradation or total power loss.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eMount the T8110B vertically into the designated processor slot of the Trusted chassis to ensure proper vertical airflow across internal heat sinks. Fasten the top and bottom mounting thumbscrews securely to bond the module enclosure directly to the rack protective grounding frame.\u003c\/p\u003e\n\u003cp\u003eRoute RS422, RS485, and IRIG-B serial connections using twisted-shielded cable pairs. Ground cable shields at a single point on the main chassis ground bus, keeping signal cabling physically isolated from high-voltage AC lines to prevent electromagnetic interference from corrupting communication frames.\u003c\/p\u003e","brand":"ICS TRIPLEX","offers":[{"title":"Default Title","offer_id":52927285133624,"sku":"T8110","price":188.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0893\/1616\/3896\/files\/102..jpg?v=1788935393","url":"https:\/\/www.automodulexpert.com\/products\/trusted-tmr-processor-module-ics-triplex-t8110b","provider":"AutoModuleXpert Ltd.","version":"1.0","type":"link"}