{"product_id":"yokogawa-cl-530-02-prosafe-sls-system-clock-module","title":"Yokogawa CL-530-02 ProSafe-SLS System Clock Module","description":"\u003ch2\u003eYokogawa CL-530-02 ProSafe-SLS Clock Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eYokogawa CL-530-02\u003c\/strong\u003e is a system clock module designed for the Yokogawa ProSafe-SLS solid-state logic solver safety system. It uses a crystal-controlled oscillator to generate two independent 1 kHz timing pulse trains (A-voltage and B-voltage) offset by 180 degrees, distributing synchronized timing signals across the internal backplane bus to connected safety logic modules.\u003c\/p\u003e\n\u003ch3\u003eClock Signal Generation and Synchronization\u003c\/h3\u003e\n\u003cp\u003eThe module produces 1 kHz A-voltage and B-voltage clock pulses with a specified frequency accuracy of 998.5 +- 0.5 Hz and a 180-degree phase shift between the two channels. Output pulses operate at 16-20 V DC with a 3.6 us pulse width measured at 10 V.\u003c\/p\u003e\n\u003cp\u003eTo support multi-module timing coordination, the CL-530-02 includes A\/B synchronization input\/output interfaces along with four Logic \"1\" current pulse outputs rated at 500 mA. Onboard frequency monitoring checks oscillator stability and triggers an SPDT alarm relay contact rated at 60 V DC \/ 48 V AC, 0.5 A if a clock fault occurs.\u003c\/p\u003e\n\u003ch3\u003ePower and Mechanical Format\u003c\/h3\u003e\n\u003cp\u003eThe module runs on a 24 V DC (+-10%) auxiliary power supply and consumes approximately 1.2 W. It is built on a Single Eurocard (6TE) form factor measuring 160 x 100 x 30 mm, weighing approximately 170 g, and connects via a 48-pin DIN 41612 Bauform F connector.\u003c\/p\u003e\n\u003cp\u003eNote that an earlier summary snippet in the source material describes the CL-530-02 as a VDC logic I\/O card for CENTUM VP measuring 120 x 80 x 25 mm and weighing 0.5 kg, which conflicts with the ProSafe-SLS clock module datasheet specifications below.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCL-530-02\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eYokogawa\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem\u003c\/td\u003e\n\u003ctd\u003eProSafe-SLS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eClock Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eClock Outputs\u003c\/td\u003e\n\u003ctd\u003eA-voltage and B-voltage pulses\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eClock Frequency\u003c\/td\u003e\n\u003ctd\u003e1 kHz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFrequency Accuracy\u003c\/td\u003e\n\u003ctd\u003e998.5 +- 0.5 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA\/B Phase Difference\u003c\/td\u003e\n\u003ctd\u003e180 deg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eClock Output Voltage\u003c\/td\u003e\n\u003ctd\u003e16-20 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePulse Width\u003c\/td\u003e\n\u003ctd\u003e3.6 us at 10 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLogic \"1\" Outputs\u003c\/td\u003e\n\u003ctd\u003e4 current pulse outputs (500 mA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSynchronization\u003c\/td\u003e\n\u003ctd\u003eA\/B synchronization input\/output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOscillator\u003c\/td\u003e\n\u003ctd\u003eCrystal-controlled\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFault Monitoring\u003c\/td\u003e\n\u003ctd\u003eFrequency monitoring\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAlarm Output\u003c\/td\u003e\n\u003ctd\u003eSPDT relay contact (60 V DC \/ 48 V AC, 0.5 A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAuxiliary Supply\u003c\/td\u003e\n\u003ctd\u003e24 V DC +-10%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e1.2 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnector\u003c\/td\u003e\n\u003ctd\u003eDIN 41612, 48-pin, Bauform F\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Format\u003c\/td\u003e\n\u003ctd\u003eSingle Eurocard, 6TE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e160 x 100 x 30 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e170 g\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-20 deg C to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-25 deg C to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What is the role of the Yokogawa CL-530-02 in a ProSafe-SLS system? A: It generates crystal-controlled 1 kHz A-voltage and B-voltage timing pulses with a 180-degree phase difference over the internal bus to synchronize ProSafe-SLS safety logic modules.\u003c\/p\u003e\n\u003cp\u003eQ: How does the CL-530-02 indicate an oscillator or frequency fault? A: Built-in frequency monitoring detects timing deviations and switches an SPDT relay alarm contact rated at 60 V DC \/ 48 V AC, 0.5 A.\u003c\/p\u003e\n\u003cp\u003eQ: What physical format and power supply does the CL-530-02 use? A: It is a 6TE Single Eurocard (160 x 100 x 30 mm) with a 48-pin DIN 41612 Bauform F connector, powered by a 24 V DC (+-10%) supply at roughly 1.2 W.\u003c\/p\u003e","brand":"YOKOGAWA","offers":[{"title":"Default Title","offer_id":51495097827640,"sku":"CL-530-02","price":265.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0893\/1616\/3896\/files\/CL-530-021.jpg?v=1765353696","url":"https:\/\/www.automodulexpert.com\/products\/yokogawa-cl-530-02-prosafe-sls-system-clock-module","provider":"AutoModuleXpert Ltd.","version":"1.0","type":"link"}